• Multifunction numerical relay
• Three-phase, low-set and high-set phase overcurrent
• Two sets of low-set and high-set setting for phase overcurrent
• Low-set and high-set earth fault
• Two sets of low-set and high-set setting for earth fault

Size:Miniature
Temperature:-5℃ to +55℃
Dimension (mm):96(w) x 96(h) x 110(d)
Rated voltage:250V AC / DC
Usage:Protective
Contact Load:Low Power
Mounting:Panel mounting
Contact rating:5 A
Theory: Electromagnetic Relay
Humidity: 56 days at 93% RH and 40℃ n
Enclosure protection: IP54 at the panel
Certifications: ISO9001
SD2200 OC&EF Protection Relay Features |
• Multifunction numerical relay
• Four selectable IDMT characteristic curves
• Definite time for low-set and high-set
• Numeric display of phase and earth fault currents
• Display of relay settings
• 9 non- volatile records of previous tripping currents
• Highly flexible programmable relay outputs
• Multifunction external digital input
• Isolated RS485 Modbus -RTU communication
• Selectable 50 Hz / 60 Hz
SD2200 OC&EF Protection Relay Show |

SD2200 OC&EF Protection Relay Specification |
Measuring Input | EARTH-FAULT ELEMENT | ||
Rated current In | 1A or5A | Low-set setting l o> | 0.05~1.0xln,step 0.01 |
Rated frequency | 50 or 60Hz | High-set setting l>>0 | 0.05~10xln,step 0.05 |
Burden | <0.3 VA at In | Time multiplier kt 0> | 0.02~1.0xln,step 0.01 |
Themal withstand | 4 x In continuous | Low-set definite time t 0>,0~300s | 0~10.0s:step 0.01 |
25xIn for less than 10 sec | 10.0~100s:step 0.1 | ||
100xIn for less than 1 sec | 100~300s: step 1 | ||
OVERCURRENT ELEMENT | High-set definite time t o>>, 0~300s | 0~10.0s:step 0.01 | |
Low-set setting l > | 0.1 A ~ 2.5xln, step 0.01 | 10.0~100s:step 0.1 | |
High-set seting l>> | 0.10 A to 40xln | 100~300s: step 1 | |
0.1 A ~ 10xln, step 0.05 | Rated auxiliary voltage | ||
10~40 ln: step0.1 | SD2200A-240A | 198~265 V AC | |
Time multiplier kt> | 0.02~1.0, step 0.01 | SD2200A-240AD | 85~265 V AC |
Low set definite time t>,0~300s | 0~10.0s: step0.01 | 110~340 V DC | |
10.0~100s: step 0.1 | Supply frequency | 50 or 60 Hz | |
100~300s: step 1 | V A rating | 3 VA typical | |
High-set definite time(t>>),0~300s | 0~10.0s step 0.01 | MECHANICAL | |
10.0~100s: step 0.1 | Mounting | panel mounting | |
100~300s: step 1 | Dimension(mm) | 142(w)x165(h)x198(d) | |
ACCURACY | Approximate weight | 2.9 kg | |
protection thresholds | ±3% | ENVIRONMENTAL CONDITIONS | |
Time delay | ±2% with a minimum of 50 ms | Temperature | -5℃ to +55℃ |
Measurements | ±3% | Humidity | 56 days at 93% RH and 40℃ non-condensing |
Reset radio | 95% typical | Binary Input | |
Overshoot time | less than 30 ms typical | External binary input | 18~265 V DC |
Power consumption | 85~265 V AC | ||
AC auxiliary voltage | 6~10VA typical | Communication | RS485 Modlbus - RTU |
DC auxiliary voltage | 5~9W typical |
—————————————SD2200 OC&EF Protection Relay Chart————————————— |
Tips: All specifications for reference only, please confirm with us before placing orders.